Machine Model: GENPWTwoAxis
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < Tdop < 0.5*Mult*TimeStep then Tdop = 0.5*Mult*TimeStep
- If 0 < Tqop < 0.5*Mult*TimeStep then Tqop = 0.5*Mult*TimeStep
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| H | Inertia constant, sec |
| D | Damping factor, pu |
| Ra | Stator resistance, pu |
| Xd | Direct axis synchronous reactance |
| Xq | Quadrature axis synchronous reactance |
| Xdp | Direct axis transient reactance |
| Xqp | Quadrature axis transient reactance |
| Tdop | Open circuit direct axis transient time constant |
| Tqop | Quadrature axis transient time constant |